FS4000/4 4-zonu analogāis ugunsdrošības panelis

FS4000/4 4-zonu analogāis ugunsdrošības panelis
FS4000/4 4-zonu analogāis ugunsdrošības panelis
Modelis: FS4000/4
Pieejamība: Pieejams
Cena: 115,00€

4 zones fire control panel FS4000 is designed to operate with conventional automatic fire detectors and manual call points. The panel has outputs provided for external executive devices.

Technical features
Fire alarm lines:
   - Maximum number of fire detectors in a line - 32
   - Connecting line - two wire
   - Maximum resistance of a line - 100 ohm

Current thresholds for:
   - Fault condition - 0-3mA
   - Duty mode - 3-12 mA
   - Fire condition - 12-80mA
   - Short circuit - >80mA
Controllable outputs for fire condition:
   - Number - 2 pcs;
   - Type - potential, relay with independent control
   - Electrical characteristics - (19-28)V DC/1 A
Relay outputs for fire condition:
   - Number - 2 pcs
   - Type - potential-free, switching with independent control
   - Electrical characteristics - 3А/125V AC, 3A/30V DC
Relay output for fault condition:
   - Number - 1 pcs
   - Type - potential-free, switching with independent control
   - Electrical characteristics - 3А/125V AC, 3A/30V DC

Performance:
-    Control over fire alarm lines and controllable outputs for fault conditions (short circuit and interruption) and automatic reset.
-    Detection of removed fire detector and automatic reset.
-    Identification of manual call points.
-    LED indication for alarm state and emergency.
-    Delay of outputs for fire condition with time period of 1, 2, 3, 4, 5, 6  or 7 minutes after fire condition is registered.
-    Option for ''LOGICAL AND '' realization of two fire alarm lines.
-    Duty Mode condition with direct activation of Fire Condition 2nd Stage '' for two fire alarm lines.
-    Status Indication of the device for data transmission RS485.
-    Option for switching  on/off  interface RS485 communication.
-    Built-in sounder for fire condition – one tonal, continuous, can be switched off.
-    Built-in sounder for fault condition – one tonal, discontinuous, can be switched off.
-    Test mode for fire alarm lines.
-    Disabling fire alarm lines.
-    Disabling outputs for fire condition.
-    Expanding the options by means of extra relay outputs for fire condition for each line and built-in RS485 for operation in a local network.

Indications of registered events:
   - Light indication - LED
   - Sound - Built-in sounder

Power supply
   - Mains:
          Voltage - (187-252)V AC
          Frequency - 50/60 Hz
   - Backup batteries:
          Battery type - lead, gel electrolyte
          Number of batteries - 2 pcs
          Nominal voltage of the backup battery - 12V
          Nominal capacity C20 - (4,5) Ah
          Charge voltage - 28V DC
          Operation in Duty mode upon interruption in main power supply:
           98 h (24V / 4,5Ah),
           24 h (24V / 1,2Ah)

   Power supply to external devices:
   - Voltage - (19-28)V DC
   - Maximum current value (including current of contr.outputs) - 1,2A

Dimension - 313х218х85  mm
Weight (backup batteries not included) - 1,5 kg

Darbojas uz OpenCart